The LR40 is Triton Controls dual pump control panel with a built-in alarm for domestic or industrial pumping stations.
The dual pump controller comes in a range of 4 products
Supply voltage | 230Vac I/III or 400Vac III -20% +30% 50/60Hz |
Supply voltage wiring size (max) | 16mm2 |
Pump current range | 1-12A |
Pump output wiring size (max) | 12mm2 |
Overload setting (Imax) | Settable between 1A to 20A |
Float switch supply voltage | 5Vdc 10mA |
Float switch and alarm output wiring size (max) | 10mm2 |
Pump Protection | Overcurrent / Over-temperature / alternating pumps |
Alarm output | 10A 250Vac or 125Vdc isolated relay output SPDT |
Alarm acoustic output | 103dB 3kHz 12Vdc piezo buzzer |
Auxiliary alarm output | 12Vdc 500mA |
IP rating | IP65 |
Size | 340mm x 300mm x 120mm |
Weight | 3.7kg |
Operational temperature range | -10°C to +55°C |
Gland configuration | Supply 1 x M25 / Pumps, inputs & outputs 6 to 9 x M16 |
Back up battery* | The alarm system is operational for >48h |